| Explosion protection marking |
I Ma k X (non-electrical part), PO Ex ia I Ma X (electrical part) |
|
Operating temperature when using extinguishing agent, °C: - "ISTO-3" VD-KP-11 - PAV10 |
from minus 20 to plus 50; from plus 4 to plus 50 |
|
Degree of protection against external influences: - for BU-1 (RO-R ASPZ) and BU-1-485 (RO ASPZ); - for housing of MUPTV-19-GZ-VD (RO ASPZ) |
IP65; IP67 (input box of electric start unit IP20) |
| Electric shock protection class | III |
|
Maximum model fire source rating: - "ISTO-3" VD-KP-11 - PAV10 |
0.7A, 233B; 0.5A, 233B |
|
Extinguishing capability for Class A and B fires when installed on ceiling or wall vertically with spray nozzle down: - installation height, m - area, m² |
from 2.5 to 6; 4 (square), 6.28 (circle) |
| Explosion-proof components and Ex-components of MUPTV: |
|
| Overall dimensions, mm | 467×340×404 |
| Extinguishing agent volume, dm3 | 19±0.1 |
|
Filled module weight, kg, not more than: - "ISTO-3" VD-KP-11; - PAV10 |
39.5; 34.2 |
* - MUPTV units may be equipped with the BU-1 (RO-R ASPZ) or BU-1-485 (RO ASPZ) control unit;
** - used as part of the enclosure of the BU-1 (RO-R ASPZ) or BU-1-485 (RO ASPZ) control unit.
Application area
Underground workings of mines and pits, and their surface structures, including those hazardous due to gas and/or dust, in accordance with the assigned explosion protection marking I Ma k X and the requirements of industry Safety Regulations.