Automatic Backup Power Input Module +12V MCS100-APS12-2 is designed for automatic switching of the working input of intrinsically safe power supply to a backup one in order to ensure Category I power supply reliability for various mine automation devices (including fire protection systems).
Discrete Input Module, 7-channel, with Line Monitoring MCS100-DI7C for receiving and processing dry contact input signals with sensor line monitoring.
Discrete Output Module, 7-channel, with Line Monitoring MCS100-DO7R is designed for controlling and powering external devices with line monitoring of their connections.
Discrete Input Module, 8-channel MCS100-DI8 for receiving and processing potential input signals.
Discrete Output Module, 8-channel MCS100-DO8 is designed for signaling and controlling dry contact signals (normally closed/open).
NAMUR Signal Input Module, 4-channel, with Line Monitoring MCS100-N4 is designed for monitoring the state of NAMUR-type sensors.
Analog Temperature Input Module, 4-channel MCS100-AI4TR is designed for receiving and processing signals from temperature sensors (resistance thermometers).
Analog Current Input Module, 4-channel MCS100-AI4i is designed for receiving and processing standard current signals: 0…5 mA, 0(4)…20 mA.
| Explosion protection marking | Ex ia I Ma U* |
| Operating temperature, °C | from minus 20 to plus 40 |
| Ingress protection rating | IP20 |
| Protection class against electric shock | III |
| Rated supply voltage, V | 12** |
| Power consumption, max, W | 1** |
| Communication interface | RS-485** |
| Communication protocol used for data transmission | ModBus-RTU; ModBus-ASCII; internal** |
| Device mounting | DIN-rail: Ω-type, width 35 mm, recommended height 7.5 mm / 15 mm |
| Overall dimensions, mm | 122×55.5×32 |
| Weight, kg | 0.13 |
|
Automatic Backup Power Input Module +12V MCS100-APS12-2 |
|
| Maximum input voltage, V | 20 |
| Maximum input current, A | 2 |
| Maximum switching power, W | 30 |
|
Discrete Input Module, 7-channel, with Line Monitoring MCS100-DI7C |
|
| Type of discrete input sensor: |
- switching devices (contacts of buttons, switches, reed switches, relays, etc.); - sensors with transistor outputs; - n-p-n type (open collector) and/or p-n-p type switches |
|
Discrete Output Module, 7-channel, with Line Monitoring MCS100-DO7R |
|
| Type of line monitoring sensor for discrete output | series-connected Diode + resistive load 1kΩ |
|
Discrete Input Module, 8-channel MCS100-DI8 |
|
| Type of connected sensor | potential |
|
Discrete Output Module, 8-channel MCS100-DO8 |
|
| Types of discrete outputs (depending on version) | normally open / normally closed |
|
NAMUR Signal Input Module, 4-channel, with Line Monitoring MCS100-N4 |
|
| Signal type | NAMUR |
|
Analog Temperature Input Module, 4-channel MCS100-AI4TR |
|
| Types of connected resistance thermometers | Pt100, Pt1000, TSM50, TSM100 |
| Measured temperature range, °C | -100..+1000 |
| Measured resistance range, Ω | 0..10000 |
| Thermotransducer connection schemes | 2-wire, 3-wire, and 4-wire |
|
Analog Current Input Module, 4-channel MCS100-AI4i |
|
| Type of connected sensor | potential |
| Types of analog current signals, mA | 0..5, 0..20, 4..20 |
* - installed in multifunctional distribution cabinet MDCS;
** - for all modules except MCS100-APS12-2.
Application area
Underground workings of mines and pits and their surface structures, including those hazardous due to gas and dust, in accordance with explosion protection marking, operating conditions, and industry Safety Regulations requirements.