| Explosion protection marking | PO Ex ia I Ma |
| Operating temperature, °C | from minus 20 to plus 60 |
| Degree of protection against external influences | IP65 (external side) |
| Electric shock protection class | III |
| Power supply | battery – 2 pcs (main and backup) |
| Battery type | Li-SOCl2 |
| Rated battery voltage, V | 3.6 |
|
Rated battery capacity, A·h: – main ER26500 «EEMB»* – backup ER14505 «EEMB»* |
19.0; 9.0 |
| Standby operation time from the main battery, months, at least | 36 |
| Rated supply circuit voltage, V | 3.3 |
| Connection interface | wireless radio interface IEEE 802.15.4 |
| Maximum IEEE 802.15.4 communication range (line of sight), m | 400 |
|
Product classification per GOST R 53325–2012: – by method of detector actuation – by nature of communication with FACP (ППКП) – by type of monitored fire characteristic – by power supply method – by addressability – by physical implementation of communication with FACP – by spectral band of electromagnetic radiation perceived by the detector’s sensing element (IPP (ИПП)) |
automatic; threshold; flame detector; from autonomous source; addressable; wireless (radio channel); multiband |
|
Peak spectral sensitivity, μm: – first reference IR channel – second reference IR channel – measuring IR channel |
4.0; 5.0; 4.4 |
| IPP sensitivity (distance ensuring stable actuation) for test fires TP-5, TP-6, m, at least | 25 |
| Response time to test fires TP-5, TP-6, s, not more than | 30 |
|
Maximum allowable background illuminance, lx, at least: – from fluorescent lamps – from incandescent lamps |
2500; 250 |
| Field of view relative to the optical axis of the sensing element, degrees, at least | 90 |
| Power removal time to switch from «Fire» to standby mode, s, at least | 3.0 |
| Standby recovery time after power removal, s, not more than | 2.0 |
|
Overall dimensions, mm: – with bracket – without bracket |
166 × 280 × 355; 140 × 200 × 105 |
| Weight, kg, not more than | 2.0 |
* – The use of batteries of other types or models is permitted only after approval by the Certification Body.
Application area
Underground workings of mines and pits, and their surface structures, including those hazardous due to gas and/or dust, in accordance with the explosion protection marking and the requirements of industry safety regulations.